L06: PID Basics + Constraints

Prerequisites: L00-L05 | Effort: 60 min | Seborg: Chapter 8


Learning Objectives

By the end of this lesson you will:

  1. βœ… Understand P, I, D controller actions and when to use each
  2. βœ… Implement PID controllers using Odibi's pid() function
  3. βœ… Recognize proportional offset and how integral action eliminates it
  4. βœ… Configure output limits and anti-windup
  5. βœ… Compare P-only vs PI vs PID control performance

Theory Recap: PID Control (Seborg Ch. 8)

PID Controller Equation:

u(t) = Kp·e(t) + Ki·∫e(t)dt + Kd·de(t)/dt

Where: - e(t) = SP - PV (error = setpoint - process variable) - Kp = Proportional gain (immediate response to error) - Ki = Integral gain (eliminates steady-state offset) - Kd = Derivative gain (anticipates future error)

Controller Actions:

Action Effect When to Use Downside
P-only Fast response Simple, stable systems Offset remains
PI Eliminates offset Most industrial loops (90%) Slower than P
PID Fastest settling Fast processes, minimal noise Sensitive to noise

Key Concepts:

Proportional Offset: - P-only control leaves steady-state error - Offset = Disturbance / Kp - Higher Kp reduces offset but can cause instability

Integral Action: - Accumulates error over time - Automatically drives offset to zero - Can cause "integral windup" when saturated

Anti-Windup: - Stops integral from accumulating when output is saturated - Essential for real controllers (valves hit 0% or 100%)

Output Limits: - Physical constraints: valves (0-100%), heaters (0-max kW) - Safety limits: max flow rates, temperatures


Odibi Hands-On

Odibi PID Syntax

- name: controller_output
  data_type: float
  generator:
    type: derived
    expression: >
      pid(
        pv=current_measurement,
        sp=setpoint_value,
        Kp=2.0,
        Ki=0.1,
        Kd=0.5,
        dt=60,              # timestep in seconds
        output_min=0,
        output_max=100,
        anti_windup=True
      )

Parameters: - pv: Process variable (measured value) - sp: Setpoint (target value) - Kp, Ki, Kd: PID tuning parameters - dt: Timestep in seconds (must match simulation timestep!) - output_min/max: Physical limits (e.g., valve 0-100%) - anti_windup: Enable anti-windup (default True)


Example 1: P-only Tank Level Control

Process: Tank level control with constant inlet disturbance

# tank_p_only.yaml
nodes:
  - name: tank_level_p_only
    read:
      format: simulation
      options:
        simulation:
          scope:
            start_time: "2024-01-01T00:00:00Z"
            timestep: "1min"
            row_count: 300  # 5 hours
            seed: 42

          entities:
            count: 1
            id_prefix: "TK-"

          columns:
            - name: entity_id
              data_type: string
              generator:
                type: constant
                value: "{entity_id}"

            - name: timestamp
              data_type: timestamp
              generator:
                type: timestamp

            - name: minutes_elapsed
              data_type: float
              generator:
                type: sequential
                start: 0
                step: 1

            # Setpoint: 50%
            - name: level_sp_pct
              data_type: float
              generator:
                type: constant
                value: 50.0

            # Tank parameters
            - name: tank_area_ft2
              data_type: float
              generator:
                type: constant
                value: 100.0

            # Inlet disturbance (step change at t=60)
            - name: inlet_flow_gpm
              data_type: float
              generator:
                type: derived
                expression: "100.0 if minutes_elapsed < 60 else 110.0"

            # P-only controller (Kp=2.0, no integral!)
            - name: level_pv_pct
              data_type: float
              generator:
                type: derived
                expression: "prev('level_pv_pct', 50.0)"

            - name: outlet_valve_pct
              data_type: float
              generator:
                type: derived
                expression: >
                  pid(
                    pv=level_pv_pct,
                    sp=level_sp_pct,
                    Kp=2.0,
                    Ki=0.0,
                    Kd=0.0,
                    dt=60,
                    output_min=0,
                    output_max=100,
                    anti_windup=True
                  )

            # Tank level dynamics (first-order)
            - name: outlet_flow_gpm
              data_type: float
              generator:
                type: derived
                expression: "outlet_valve_pct * 1.5"

            - name: level_pv_pct_updated
              data_type: float
              generator:
                type: derived
                expression: >
                  max(0, min(100,
                    prev('level_pv_pct', 50.0) +
                    (inlet_flow_gpm - outlet_flow_gpm) / tank_area_ft2
                  ))

            # Update state variable
            - name: level_pv_pct
              data_type: float
              generator:
                type: derived
                expression: "level_pv_pct_updated"

            # Calculate error
            - name: error_pct
              data_type: float
              generator:
                type: derived
                expression: "level_sp_pct - level_pv_pct"

    write:
      connection: local
      format: parquet
      path: data/output/tank_p_only.parquet
      mode: overwrite

Working example: /examples/cheme_course/L06_pid_basics/tank_p_only.yaml

What you'll see: - Level starts at 50% (setpoint) - At t=60 min, inlet flow increases 10% - P-only controller cannot eliminate offset - New steady-state level β‰ˆ 55% (5% offset remains)


Example 2: PI Controller Eliminates Offset

Same tank, now with integral action:

# tank_pi.yaml (excerpt - see full file)
- name: outlet_valve_pct
  data_type: float
  generator:
    type: derived
    expression: >
      pid(
        pv=level_pv_pct,
        sp=level_sp_pct,
        Kp=2.0,
        Ki=0.1,        # Add integral action!
        Kd=0.0,
        dt=60,
        output_min=0,
        output_max=100,
        anti_windup=True
      )

Working example: /examples/cheme_course/L06_pid_basics/tank_pi.yaml

What you'll see: - Level starts at 50% (setpoint) - At t=60 min, inlet flow increases 10% - PI controller drives level back to exactly 50% - Integral action accumulates error and eliminates offset - Takes ~100 minutes to settle


Example 3: PID for Fast Response

Add derivative action for faster settling:

# tank_pid.yaml (excerpt - see full file)
- name: outlet_valve_pct
  data_type: float
  generator:
    type: derived
    expression: >
      pid(
        pv=level_pv_pct,
        sp=level_sp_pct,
        Kp=2.0,
        Ki=0.1,
        Kd=0.5,        # Add derivative action!
        dt=60,
        output_min=0,
        output_max=100,
        anti_windup=True
      )

Working example: /examples/cheme_course/L06_pid_basics/tank_pid.yaml

What you'll see: - Faster settling time (~60 minutes vs ~100 for PI) - Less overshoot - Derivative "anticipates" error trend


Data Engineering Insights

Why PID simulation matters for data engineers:

  1. Understand control outputs in historian data
  2. Why does valve position oscillate?
  3. Why is there steady-state offset?
  4. Is controller poorly tuned or is there a fault?

  5. Validate DCS logic during migrations

  6. Simulate legacy controller before cutover
  7. Generate test data for new SCADA system
  8. Verify anti-windup logic works

  9. Synthetic data for ML training

  10. Generate realistic controller behavior
  11. Include disturbances, setpoint changes
  12. Train anomaly detectors on normal operation

  13. Digital twin initialization

  14. Simulate startup sequences
  15. Test operator training scenarios
  16. Validate control logic before deployment

Exercises

Exercise 1: Verify Proportional Offset

Run tank_p_only.yaml with different Kp values (1.0, 2.0, 5.0). Calculate steady-state offset for each. Does higher Kp reduce offset?

Exercise 2: Integral Windup Demo

Modify tank_pi.yaml: - Set anti_windup=False - Add large disturbance at t=100 - Compare settling time with/without anti-windup

Exercise 3: Derivative Kick

Modify tank_pid.yaml: - Add setpoint step change at t=150 (50% β†’ 60%) - Does derivative cause large "kick" in valve output? - How would you filter the setpoint to prevent this?

Exercise 4: Output Saturation

Set inlet flow to 200 gpm (very large disturbance). Watch valve saturate at 100%. Does integral keep accumulating?


Reflection: Real Plant Scenarios

When do you see these issues?

Issue Plant Example
P-only offset Old pneumatic controllers (3-15 psi signal)
Integral windup Valve stuck, controller keeps cranking output
Derivative noise Noisy flow sensor causes valve "hunting"
Output saturation Heater maxed out, cannot reach setpoint

Red flags in historian data: - Controller output stuck at 0% or 100% β†’ Saturation - PV oscillates around SP β†’ Excessive Kd or noise - Steady offset from SP β†’ P-only or broken integral


Summary

Key Takeaways: - βœ… P-only is fast but leaves offset - βœ… PI eliminates offset (use for 90% of loops) - βœ… PID adds speed but sensitive to noise - βœ… Always use output limits and anti-windup - βœ… Odibi's pid() function handles state management automatically

Next Lesson: L07: Tuning Methods - How to calculate Kp, Ki, Kd values